Welcome to HMJ Fire Safety Services

Fire Alarm System

Panels


Overview

CE approved Single Loop Analogue addressable fire alarm panel with 127 devices of any combination with 20 loop powered sounders in addition .supports single repeater panel,Touch key panel with USB inbuilt for Laptop connectivity. Front Panel programmable.


Features

  • - Switched mode power supply
  • - Modular Construction, Serviceability
  • - Surge Protection.
  • - Battery polarity and deep discharge protection.
  • - Unique protocol feature for fast alarm response.
  • - Touch Keypad for user friendly operation.
  • - Auto learning facility

Electrical Specification

Primary Power

120 / 220VAC + 10% -15%, 60 / 50 Hz

Standby Power

12V DC(1 No. of 12V,4.5Ah Sealed Lead acid battery)

Operating Condition

Operating Temperature : 0-49 C/32-120 F.
Relative Humidity : 93 2% RH (non-condensing) at 32 2 C/ 90 3 F.

Signaling Line Circuits

Class A or Class B wiring.
No Devices : Max. 127 devices exclusive of loop sounder
Loop resistance : 40? (Max.).
Loop capacitance : 0.6 f (Max.).
Loop Current : 300mA (Max.).

Notification Appliance Circuits

Class B, Style Y wiring
Operating Nominal Voltage : 24 VDC
Current for NAC : 1.0A
Line Drop : 2.4V
End-Of-Line Resistor : 4K7, watt

D.C. Output

24VDC regulated, 300mA Max.
Type : Form C
No of Relays : 1
Relay Contact Rating : 2A @ 30 VDC,0.5A @ 125VAC

Contact Us for Enquiry

Interested in buying our PRODUCTS

Have a Question?

+91 99343 65994

Testimonials and Reviews

Words From Our Customers

Our Clients Have Always Trusted and Belived in our Fire Fighting Services